PROPERTY: ACME Facilty
LOCATION: NewYork
PROGRAM: Special Case Resources (SCR)
STEP #
1
2
3
4
5
5.1
5.2
5.3
5.4
6
6.1
6.2
7
EQUIPMENT INVOLVED
Chillers
Cooling Tower
Chilled Water Pumps
Condenser Pumps
Air Handling Units
Air Handling Units
Air Handling Units
Air Handling Units
Air Handling Units
Exhaust/Relief Fans
Exhaust/Relief Fans
Exhaust/Relief Fans
Lobby Desk/Escalator
CURTAILMENT ACTION
Make sure the electric chiller is off, and the entire cooling load
is covered by the steam chiller(s).
Increase condenser water temperature by 5 deg. F to reduce
CT fan speed. Ensure chillers can continue to produce required
tonnage. The chillers will consume additional steam.
Disable chilled water pumps as possible
Disable condenser water pumps as possible
If setpoint is > 85%, reduce to 70%.
If setpoint is < 85% reduce by 15%, for the following units:
AC -1 thru AC -4
AC -5, 6, 7, 13 , 14
AC -8
AC -9, 16% AC -17
Disable the following units
RF -6, 3, 4, 10
RF -18, 20
Reduce/Shut off lighting